Set-Up & Operation ManualLectroCount LCR-II® Electronic RegisterOperation: EM100-11www.lcmeter.com

Pagina 2 - Table of Contents

10Lap Pad Calibration & Set-UpSTEP 2: SECURITYPress the M1 Key to access a top-level menu. Press iiiii to scroll to the SECURITY menu. Press ENT

Pagina 3 - Software License Agreement

11STEP 3: GENERAL SETUP CONTINUEDPress iiiii and the cursor will move to:TIME HH:MM:SSThis field is used to set the LCR-II internal clock. The time, l

Pagina 4 - LCR-II System Components

12PRESET^Available preset options include NET, BOTH, GROSS, and NONE. Selecting NONE will disablepresetting. Presetting NET, GROSS, or BOTH is allowed

Pagina 5 - LCR-II Overview

13Lap Pad Calibration & Set-upSTEP 3: GENERAL SETUP CONTINUEDHDR^This field is used to select the line number of the ticket header that will be ed

Pagina 6 - Lap Pad Operation

14Lap Pad Calibration & Set-upSTEP 4: SYSTEM CALIBRATIONFrom the top-level menu, use iiiii to scroll to SYSTEM CALIBRATION. Press ENTER and the cu

Pagina 7

15Lap Pad Calibration & Set-upSTEP 4: SYSTEM CALIBRATION CONTINUEDDECIMAL^This field allows you to choose between whole units, tenths and hundredt

Pagina 8

16STEP 4: SYSTEM CALIBRATION CONTINUEDT UNIT^This field allows you to choose the temperature units - Degrees Fahrenheit or Degrees Celsius. PressENTER

Pagina 9 - BEFORE GETTING STARTED

17Lap Pad Calibration & Set-upSTEP 5: PRODUCT & SHIFT INFORMATIONPress ENTER and the cursor will move to:#^ (Product Number)This field is used

Pagina 10 - STEP 3: GENERAL SETUP

18Lap Pad Calibration & Set-upSTEP 5: PRODUCT & SHIFT INFORMATION CONTINUEDUNITS^From this field, a unit of measure is selected. Choose GALLO

Pagina 11

19Lap Pad Calibration & Set-upSTEP 6: PRODUCT CALIBRATIONPress M1 to return to the top-level menu. Press i to scroll to PRODUCT CALIBRATION.There

Pagina 12

2Table of ContentsDescription Page NumberLCR-II System Components 4LCR-II Specifications 5Lap Pad Operation 6-8Lap Pad Overview 6Navigating Top-Level

Pagina 13 - VOL CORRECTED MSG?

20Lap Pad Calibration & Set-upSTEP 6: PRODUCT CALIBRATION CONTINUEDCOMPENSATION TYPE^ CONTINUEDScroll through the choices: Linear F, Linear C, API

Pagina 14 - STEP 4: SYSTEM CALIBRATION

21Lap Pad Calibration & Set-upSTEP 6: PRODUCT CALIBRATION CONTINUEDPRESETThe Gross Preset amount is entered here. When this amount is reached the

Pagina 15

22Lap Pad Calibration & Set-upSTEP 6: PRODUCT CALIBRATION CONTINUEDAUX MULTThis field is used to convert the quantity delivered, (e.g. GALLONS, LI

Pagina 16

23Lap Pad Calibration & Set-upSTEP 6: PRODUCT CALIBRATION CONTINUEDPT^This field is used to calibrate the meter/register at up to 10 different flo

Pagina 17

24Lap Pad Calibration & Set-upMulti-point calibration allows a flowmeter to be used over a wide range of flow rates without experiencing a loss in

Pagina 18 - CLR SHIFT?

25Lap Pad Calibration & Set-upMULTI-POINT CALIBRATION CONTINUEDStep 5:Refill the prover at the same flow rate as Step 4 to verify that the meter r

Pagina 19 - STEP 6: PRODUCT CALIBRATION

26Lap Pad Calibration & Set-upMULTI-POINT CALIBRATION CONTINUEDStep 5:Set the LINEAR^ field to APPLIED and enter it. This puts the linearizing al

Pagina 20

27Lap Pad Basic OperationPRESET DELIVERY WITH A LAP PAD CONTINUEDPRODUCT TYPE^This field displays the product type previously selected in CALIBRATION.

Pagina 21

28Lap Pad Basic OperationPRESET DELIVERY WITH A LAP PAD CONTINUEDPRESETThe PRESET amount can be entered here. A preset of GROSS or BOTH must have bee

Pagina 22 - %Error =

29Diagnostics/Factory CalibrationMost of the DIAGNOSTICS fields are for DISPLAY ONLY. They contain information that can be useful in troubleshooting.

Pagina 23

3Software License Agreement1. Liquid Controls hereby grants to Licensee a nonexclusive license to use SR260 (hereinafter referred toas “Licensed Softw

Pagina 24 - MULTI-POINT CALIBRATION

30Diagnostics/Factory CalibrationDIAGNOSTICS CONTINUEDPULSR FAULTSThis field displays the number of quadrature pulser faults detected during the last

Pagina 25

31Recalibration/Proving without a Lap PadThe addition of two control buttons on the front panel of the LCR-II allows for single point recalibration or

Pagina 26 - Lap Pad Basic Operation

32Recalibration/Proving without a Lap PadSINGLE POINT RECALIBRATION/PROVING CONTINUEDPress SELECT to advance to:Calibration - Screen 1, Product Number

Pagina 27

33Recalibration/Proving without a Lap PadNOTE: If the new value entered is out of range for theLCR-II, "Error" will appear in the display.

Pagina 28

34Basic Operation without a Lap PadOnce the LCR-II has been calibrated, a Lap Pad is not required for daily use of the register. There are two push b

Pagina 29 - DIAGNOSTICS

35Basic Operation without a Lap PadDELIVERY & SELECTIONS MENU CONTINUEDRUN Position (Flowrate/Temp.) ContinuedPress SELECT a second time (within 5

Pagina 30 - DIAGNOSTICS CONTINUED

36Basic Operation without a Lap PadDELIVERY & SELECTIONS MENU CONTINUEDPRINT Position (Product #/Totalizer)Turning the Selector Switch to the PRIN

Pagina 31

37Basic Operation without a Lap PadDELIVERY & SELECTIONS MENU CONTINUEDPRINT Position (Product #/Totalizer) ContinuedA shift ticket is printed whe

Pagina 32

38LCR-II Menu Flow ChartsSelector Switch STOP Position of Selector Switch22345.6DELIVERY TOTALProd 1PRODUCT NUMBERProd 2PRODUCT NUMBERProd 3PRODUCT NU

Pagina 33 - CONTINUED

39L6789.0GROSS OR NET TOTALIZERH12345GROSS OR NET TOTALIZERProd 1PRODUCT NUMBERProd 4PRODUCT NUMBERSELECTSELECTSELECTINCREASEINCREASE(If System is“Loc

Pagina 34 - RUN Position (Flowrate/Temp.)

4LCR-II System ComponentsPump & PrintCommunication andProgramming DevicesLap Pad Hand Held Computer Laptop Computer

Pagina 35

40LCR-II Troubleshooting GuideThe LCR-II troubleshooting guide covers most common problem situations. Call your local Liquid Controls ServiceCenter o

Pagina 36 - 11:44:00

41NOTE: Check for proper operating voltages before changing the circuit board. If the circuit board needs to be changed,be sure to remove all power t

Pagina 37

42LCR-II Troubleshooting GuidePower to LCR-II interrupted during delivery.1. Check accessory power cable for damage. Ensure that the power, common an

Pagina 38 - SELECT: Step through digits

43LCR-II Troubleshooting GuidePulser failure. 2. If the LCR-II display counter increments, this may indicate a mechanical problem. Contact your loca

Pagina 39

44LCR-II Troubleshooting Guide1. Insert a delivery ticket into the Epson printer and start a delivery.Foreign debris in system. 2. Move the selector

Pagina 40 - LCR-II Troubleshooting Guide

45Appendix A - Compensation Types & ParametersThe table below shows the supported methods of calculating the Volume Correction Factor (VCF). The

Pagina 41

46Appendix B - Operation Using VT 100 Compatible TerminalIf the LCR-II is operated using a VT 100 compatible terminal (instead of the LC Lap Pad), ref

Pagina 42

47Appendix C - Error MessagesThe LCR-II was designed to perform diagnostic analysis of problems as they occur. If an error should occur, one of thefo

Pagina 43 - SOLUTIONPROBABLE CAUSEPROBLEM

48Appendix C - Error MessagesIf an error occurs during a delivery, the message "*FAULT: PRINT DIAGNOSTICS TICKET*" will appear on the delive

Pagina 44

49Appendix C - Error MessagesDIAGNOSTIC MESSAGE LIST CONTINUEDDELIVERY END REQSTThis message appears when a PRINT command has been sent to the LCR-II

Pagina 45

5LCR-II OverviewThis manual provides instructions for the initial setup, the calibration, and the operation of LectroCount LCR-II software,also known

Pagina 46

50Appendix C - Error MessagesDIAGNOSTIC MESSAGE LIST CONTINUEDNET PRESET ACTIVEThis message appears when a NET PRESET is active. The PRESET type must

Pagina 47 - Appendix C - Error Messages

51Appendix D - Lap Pad Menu Flow ChartsGENERAL SETUPPress Enter or Scroll with ARROW keys.SYSTEM CALIBRATIONPress Enter or Scroll with ARROW keys.PROD

Pagina 48

52Appendix D - Lap Pad Menu Flow ChartsDELIVERY & PRESETPress Enter or Scroll with ARROW keys.PRICE/UNIT TAX/UNIT % TAX 0.0000

Pagina 49

53Appendix D - Lap Pad Menu Flow ChartsPRODUCT & SHIFT#^ SHIFT GROSS SHIFT NET UNITS^1 0.0 0.0 GALLONS#^ GROSS

Pagina 50

54Appendix D - Lap Pad Menu Flow ChartsGENERAL SETUPPRINT GROSS & PARAM? VOL CORRECTED MSG?YES YESSALE # TICKET # UNIT ID

Pagina 51

55Appendix D - Lap Pad Menu Flow ChartsSYSTEM CALIBRATIONCALIB # CALIB EVENT CONFIG EVENT 1 17 41UNITS^ RATE BASE^

Pagina 52 - • Scroll Forward one position

56Appendix D - Lap Pad Menu Flow ChartsPRODUCT CALIBRATIONENTERM# M1M1M1M1M#PRODUCT CALIBRATIONPress Enter or Scroll with ARROW keys.#^ CODE PRODU

Pagina 53 - PRODUCT & SHIFT

57SECURITYFACTORYDIAGNOSTICSAppendix D - Lap Pad Menu Flow ChartsDIAGNOSTICSPress Enter or Scroll with ARROW keys.SOFTWARE LANGUAGE TICKETSR2

Pagina 54 - GENERAL SETUP

58This guide has been created to clearly convey the method for proving a meter system equipped with a LectroCountLCR-II electronic register without th

Pagina 55 - SYSTEM CALIBRATION

59k-Factor Adjustment Example:Presume that the LCR-II register displayed "101.235" Units and the prover volume was determined to be "10

Pagina 56 - PRODUCT CALIBRATION

6Lap Pad OperationThis section of the manual provides instructions for theinitial set-up, calibration and operation of your LCR-IIElectronic Register

Pagina 57

© 2006 Liquid ControlsPub. No. 500302(7/12)CORKEN3805 Northwest 36th St.Oklahoma City, OK 73112(405) 946-5576FAURE HERMANRoute de BonnetableB.P. 20154

Pagina 58

7When the LCR-II is powered up with a Lap Pad attached, the Lap Pad will briefly display a copyright message for twoseconds followed by the initial to

Pagina 59

8Each of the top-level menus has a secondary level consisting of one or more screens. Each screen is divided into oneor more fields where data may be

Pagina 60

9Lap Pad Calibration & Set-Up• Make sure that the Lap Pad or other data entry device is connected to the LCR-II register as described in the LCR-I